To calculate airflow in CFM, multiply the air velocity in feet per minute (FPM) by the duct's cross-sectional area in square feet: CFM = FPM × ft². A 12-inch round duct has an area of 0.785 ft², so at 800 FPM it carries 628 CFM. Use the inside diameter and the average velocity across the duct, as a single centreline reading runs high. The calculator also gives m³/h and L/s.
Already have a figure to convert? Use the CFM to m³/h and m³/h to CFM converters.
Enter values to calculate
Air flow resultsFree download
Schedule 40 pipe sizes, water flow in GPM and LPM at four design velocities, and recommended velocities by application. One PDF, made to pin above the bench.
Multiply the velocity by the duct's cross-sectional area. L/s = m/s × area in m² × 1,000. A 300 mm round duct has an area of 0.0707 m², so at 5 m/s it carries 353.4 L/s, which is 1,272 m³/h or 749 CFM. With imperial units, CFM = FPM × area in ft², and 1 m/s is 196.85 FPM.
Use the calculator to turn an anemometer reading in a duct into CFM, m³/h or L/s, to check a design velocity against the ranges below, or read a duct size off the tables for a target airflow. It multiplies the average velocity by the duct's cross-sectional area and converts the units.
Q = V × A
Where:
A = π × D² / 4
Where D is the internal duct diameter. For example, a 300 mm diameter circular duct has a cross-sectional area of 0.0707 m².
A = W × H
Where W is duct width and H is duct height. A 400 mm × 200 mm rectangular duct has an area of 0.08 m².
When comparing rectangular and circular ducts, the equivalent diameter for equal friction loss is:
D_eq = 1.30 × (W × H)^0.625 / (W + H)^0.250
| Application | m/s | FPM |
|---|---|---|
| Residential supply ducts | 2 to 4 | 400 to 800 |
| Commercial supply ducts | 5 to 8 | 1,000 to 1,600 |
| Main supply trunks | 6 to 10 | 1,200 to 2,000 |
| Return air ducts | 3 to 5 | 600 to 1,000 |
| Exhaust ducts | 5 to 10 | 1,000 to 2,000 |
| Industrial ventilation | 10 to 20 | 2,000 to 4,000 |
Higher velocities reduce duct size but increase noise and pressure drop. Branches and outlets serving occupied rooms are usually kept below about 7.5 m/s (1,500 FPM) to limit noise; ASHRAE sets the limit by duct location and the room's noise criterion.
CFM = FPM × area in ft², for the inside diameter of a round duct. Read across at the velocity your design uses.
| Duct (in) | Area (ft²) | 600 FPM | 800 FPM | 1,000 FPM |
|---|---|---|---|---|
| 4 | 0.087 | 52 CFM | 70 CFM | 87 CFM |
| 5 | 0.136 | 82 CFM | 109 CFM | 136 CFM |
| 6 | 0.196 | 118 CFM | 157 CFM | 196 CFM |
| 7 | 0.267 | 160 CFM | 214 CFM | 267 CFM |
| 8 | 0.349 | 209 CFM | 279 CFM | 349 CFM |
| 9 | 0.442 | 265 CFM | 353 CFM | 442 CFM |
| 10 | 0.545 | 327 CFM | 436 CFM | 545 CFM |
| 12 | 0.785 | 471 CFM | 628 CFM | 785 CFM |
| 14 | 1.069 | 641 CFM | 855 CFM | 1,069 CFM |
| 16 | 1.396 | 838 CFM | 1,117 CFM | 1,396 CFM |
| 18 | 1.767 | 1,060 CFM | 1,414 CFM | 1,767 CFM |
| 20 | 2.182 | 1,309 CFM | 1,745 CFM | 2,182 CFM |
| 24 | 3.142 | 1,885 CFM | 2,513 CFM | 3,142 CFM |
L/s = m/s × area in m² × 1,000, and m³/h = L/s × 3.6, for the inside diameter of a round duct.
| Duct (mm) | Area (m²) | 2 m/s | 3 m/s | 5 m/s |
|---|---|---|---|---|
| 100 | 0.0079 | 15.7 L/s (57 m³/h) | 23.6 L/s (85 m³/h) | 39.3 L/s (141 m³/h) |
| 125 | 0.0123 | 24.5 L/s (88 m³/h) | 36.8 L/s (133 m³/h) | 61.4 L/s (221 m³/h) |
| 150 | 0.0177 | 35.3 L/s (127 m³/h) | 53.0 L/s (191 m³/h) | 88.4 L/s (318 m³/h) |
| 160 | 0.0201 | 40.2 L/s (145 m³/h) | 60.3 L/s (217 m³/h) | 100.5 L/s (362 m³/h) |
| 200 | 0.0314 | 62.8 L/s (226 m³/h) | 94.2 L/s (339 m³/h) | 157.1 L/s (565 m³/h) |
| 250 | 0.0491 | 98.2 L/s (353 m³/h) | 147.3 L/s (530 m³/h) | 245.4 L/s (884 m³/h) |
| 315 | 0.0779 | 155.9 L/s (561 m³/h) | 233.8 L/s (842 m³/h) | 389.7 L/s (1,403 m³/h) |
| 400 | 0.1257 | 251.3 L/s (905 m³/h) | 377.0 L/s (1,357 m³/h) | 628.3 L/s (2,262 m³/h) |
| 500 | 0.1963 | 392.7 L/s (1,414 m³/h) | 589.0 L/s (2,121 m³/h) | 981.7 L/s (3,534 m³/h) |
| 630 | 0.3117 | 623.4 L/s (2,244 m³/h) | 935.2 L/s (3,367 m³/h) | 1,558.6 L/s (5,611 m³/h) |
Common questions about calculating air flow in CFM, m³/h and L/s.
Multiply the air velocity in feet per minute (FPM) by the duct's cross-sectional area in square feet. A round duct's area is π × D² ÷ 4 with D in feet, so a 12-inch duct is 0.785 ft² and at 800 FPM carries 628 CFM. For a rectangular duct, multiply width by height: a 16 × 8 inch duct is 0.889 ft² and at 800 FPM carries 711 CFM.
1 CFM equals 1.699 m³/h, and 1 m³/h equals 0.5886 CFM. For L/s, 1 CFM is 0.4719 L/s and 1 L/s is 2.119 CFM.
Volumetric air flow is measured in CFM (cubic feet per minute) in the US, m³/h in most of Europe, and L/s in the UK, Australia and many ISO standards; large plant also uses m³/s. Air velocity is measured in m/s or FPM, and it becomes a flow rate only once it is multiplied by the duct area. Psychrometric and heat load calculations work in mass flow (kg/s or lb/h), which stays the same as the air warms or cools.
Multiply the room volume in cubic feet by the air changes per hour (ACH) you need, then divide by 60: CFM = ft³ × ACH ÷ 60. A 10 × 10 ft room with an 8 ft ceiling is 800 ft³, so 6 air changes an hour needs 800 × 6 ÷ 60 = 80 CFM. Take the ACH from the ventilation standard or the duty the room serves.
Residential supply ducts typically run at 2 to 4 m/s (400 to 800 FPM), commercial supply ducts at 5 to 8 m/s (1,000 to 1,600 FPM), and industrial ventilation at 10 to 20 m/s (2,000 to 4,000 FPM). Branches and outlets serving occupied rooms are usually kept below about 7.5 m/s (1,500 FPM) to limit noise; ASHRAE sets the limit by duct location and the room's noise criterion.
The calculator works in volumetric flow, taken from the velocity and area you enter, so temperature does not change its result. The mass of air moved does change: air density is about 1.225 kg/m³ at 15 °C and 1.127 kg/m³ at 40 °C at sea level. For heating and cooling loads, account for the density difference between supply and return air.
Pressure drop in a duct rises roughly with the square of velocity, so doubling the air velocity roughly quadruples the pressure drop. Smaller ducts save material but need more fan power to overcome the higher pressure drop, so duct size is a balance against fan energy.
Add this free calculator to your website. Copy the code below and paste it into your page.
Continue your analysis with these related engineering tools
Convert cubic feet per minute to cubic metres per hour
Convert cubic metres per hour to cubic feet per minute
Calculate fluid velocity and Reynolds number
Convert inches of water column to psi
Convert psi to inches of water column
© 2026 Flow Rate Calculator. All rights reserved. A Nomogram Works site.